To use a power generator as a power source for your pump, you must follow the power on/off process.
Power On:
First, turn on the generator and allow it to warm up for at least 1 minute to allow the power to stabilize. Then, you may turn on the pump.
Power Off:
Reverse the above process. First turn off the pump, then turn off the generator.
We recommend that you install a 2-pole(for single phase) or a 3-pole(for 3-phase) switch in between the generator and the control box for switching On / Off the pump.
Below is a table that lists the minimum generator requirements for Tuhorse Pumps.
Pump | Minimum Generator Requirement | ||
HP | KW | HP | KW |
0.75 | 0.55 | 3 | 2.2 |
1 | 0.75 | 4 | 3 |
1.5 | 1.1 | 5 | 4.5 |
2 | 1.5 | 7 | 5.5 |
3 | 2.2 | 10 | 7.75 |
5 | 3.7 | 15 | 11 |
7.5 | 5.5 | 23 | 16.5 |
10 | 7.5 | 30 | 22.5 |
15 | 11 | 45 | 33 |
20 | 15 | 60 | 45 |
25 | 18.5 | 75 | 55.5 |
30 | 22 | 100 | 75 |
40 | 30 | 120 | 90 |
50 | 37 | 150 | 111 |
60 | 45 | 180 | 135 |
75 | 55 | 225 | 165 |
100 | 75 | 300 | 225 |
125 | 93 | 375 | 280 |